Permit Number: TC-COM-0624-01171
Parcel: 11012007B

Address:
5151 E GRANT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0624-01171
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/22/2025 Commercial Mechanical REQUIRES RESUBMIT Comment not addressed. [Initial comment: The prep area has two Turbo Chef ovens. Provide general room exhaust for any cooking appliance that does not require the installation of a Type II hood. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.1, exception 2 and 507.3, IMC 2018.]
05/22/2025 Commercial Structural REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Building Review comments were addressed. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
12. Please show a section detail of the knee and toe clearance provided at the accessible seating area at the bar.
13 Please amend plans to show a handrail extension at the top of the stairs and ramps as well as the bottom. (Please provide details of ramp/stair handrail extension termination. 2009 ICC A117.1 505.10)
25. Sheet A1.0, Sheet ID601: The accessible 36” width appears to be interrupted by the 10” wide 42inch high Counter. Please adjust so a portion of the counter surface, 36 inches minimum in length and 36 inches maximum in height above the floor shall be provided.
27. Please provide with next submittal, as this was not addressed with this submittal. (Previous comment Sheet S1.0 & S1.1: Please provide the structural calculations used for the design of the new lintels over the new openings. IBC 107.2.1)
28. Please provide with next submittal, as this was not addressed with this submittal. (Sheet S1.0 & S1.1: Please indicate on the plan the special inspections that are required for this project. IBC Chapter 17) Additionally, Please amend the Special Inspections area to list the required special inspections.
Additionally, provide the City of Tucson Special Inspection Certificate(s) with Parts A and B
completed with the next submittal. IBC 107.1 SI form link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf
New comment from 3rd review 5/22/2025
Please detail glass panels at stairways and ramps, identifying the attachment system and glazing thickness and type. IBC 2406 and IBC 2407
05/14/2025 PDSD Application Completeness Express REVIEW COMPLETED