Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.4
Permit Number - TC-COM-0624-01170
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/05/2024 | Site Zoning | APPROVED | MASTER SET LOCATED AT: TC-COM-0624-01170 with reviews to be performed for permits: TC-COM-0824-01523 , TC-COM-0824-01524, TC-COM-0824-01525, TC-COM-0824-01526, TC-COM-0824-01527, TC-COM-0824-01539, TC-COM-0824-01540, TC-COM-0824-01541, TC-COM-0824-01543 | ||
09/09/2024 | Water - PDSD | APPROVED | MASTER SET LOCATED AT: TC-COM-0624-01170 with reviews to be performed for permits: TC-COM-0824-01523 , TC-COM-0824-01524, TC-COM-0824-01525, TC-COM-0824-01526, TC-COM-0824-01527, TC-COM-0824-01539, TC-COM-0824-01540, TC-COM-0824-01541, TC-COM-0824-01543 | ||
09/12/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | MASTER SET LOCATED AT: TC-COM-0624-01170 with reviews to be performed for permits: TC-COM-0824-01523 , TC-COM-0824-01524, TC-COM-0824-01525, TC-COM-0824-01526, TC-COM-0824-01527, TC-COM-0824-01539, TC-COM-0824-01540, TC-COM-0824-01541, TC-COM-0824-01543 | ||
09/12/2024 | Commercial Electrical | REQUIRES RESUBMIT | MASTER SET LOCATED AT: TC-COM-0624-01170 with reviews to be performed for permits: TC-COM-0824-01523 , TC-COM-0824-01524, TC-COM-0824-01525, TC-COM-0824-01526, TC-COM-0824-01527, TC-COM-0824-01539, TC-COM-0824-01540, TC-COM-0824-01541, TC-COM-0824-01543 Sheet E2 Smoke detectors are to be outside area of sleeping room, Location of CO detector should be a combination CO/SD and located a minimum of 3' from bathroom doors and mechanical registers to comply with alarm requirements and 2018 IRC 314 & 315. (BM) |
||
09/12/2024 | Commercial Mechanical | REQUIRES RESUBMIT | MASTER SET LOCATED AT: TC-COM-0624-01170 with reviews to be performed for permits: TC-COM-0824-01523 , TC-COM-0824-01524, TC-COM-0824-01525, TC-COM-0824-01526, TC-COM-0824-01527, TC-COM-0824-01539, TC-COM-0824-01540, TC-COM-0824-01541, TC-COM-0824-01543 Sheet A3 Scope of work identifies new EF and dryer duct. Provide for review details and notes on plans for dryer duct installation, backdraft damper and termination to comply with 2018 IMC 504.4 & 504.8 (BM) |
||
09/12/2024 | Commercial Plumbing | REQUIRES RESUBMIT | MASTER SET LOCATED AT: TC-COM-0624-01170 with reviews to be performed for permits: TC-COM-0824-01523 , TC-COM-0824-01524, TC-COM-0824-01525, TC-COM-0824-01526, TC-COM-0824-01527, TC-COM-0824-01539, TC-COM-0824-01540, TC-COM-0824-01541, TC-COM-0824-01543 Sheet P2 Plan identifies new stack washer / dryer appliance. Will need to provide a water supply and DWV system design / schematic on plans for review. Washer will require WHA valves per 2018 IPC section 604, 604.9 and section 704 . (BM) |
||
09/12/2024 | Commercial Structural | REQUIRES RESUBMIT | MASTER SET LOCATED AT: TC-COM-0624-01170 with reviews to be performed for permits: TC-COM-0824-01523 , TC-COM-0824-01524, TC-COM-0824-01525, TC-COM-0824-01526, TC-COM-0824-01527, TC-COM-0824-01539, TC-COM-0824-01540, TC-COM-0824-01541, TC-COM-0824-01543 Sheet CS For questions in regards to plan review comments, please contact Bill McClellan by email at bmcclellan@willdan.com or cell (928)58 1. Sheet CS Occupancy should be listed as an R2 per 2018 IBC 310.3 (BM) 2. Sheet A3 Scope of work identifies new CU and to be located 10' from building exhaust. Clarify if new unit is replaced in existing location. If roof installation is a new location, provide structural evaluation for new load on roof. Electrical plan will need to identify new electrical disconnect and maintenance receptacle per 2017 NEC 210.63 & 422.30 (BM) |
||
08/12/2024 | Fire New Construction | REVIEW COMPLETED | MASTER SET LOCATED AT: TC-COM-0624-01170 with reviews to be performed for permits: TC-COM-0824-01523 , TC-COM-0824-01524, TC-COM-0824-01525, TC-COM-0824-01526, TC-COM-0824-01527, TC-COM-0824-01539, TC-COM-0824-01540, TC-COM-0824-01541, TC-COM-0824-01543 | ||
08/08/2024 | PDSD Application Completeness | REVIEW COMPLETED | |||
09/12/2024 | Site Landscape | REVIEW COMPLETED | MASTER SET LOCATED AT: TC-COM-0624-01170 with reviews to be performed for permits: TC-COM-0824-01523 , TC-COM-0824-01524, TC-COM-0824-01525, TC-COM-0824-01526, TC-COM-0824-01527, TC-COM-0824-01539, TC-COM-0824-01540, TC-COM-0824-01541, TC-COM-0824-01543 |