Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0624-01169
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/16/2024 | Site Zoning | APPROVED | |||
07/24/2024 | Water - PDSD | APPROVED | |||
07/24/2024 | Site Engineering | NOT REQUIRED | |||
07/24/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
07/05/2024 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | 1. General: At least 5% of the dining surfaces are required to have mobility features. Provide calculations of the required amount of accessible seating and indicate the locations including the bar. Additionally, ensure that surfaces are properly dispersed throughout the structure. Section 226.1 and 226.2 of the 2010 ADAAG. 2. General: The plans indicate the installation of a ramp. Provide a detailed section drawing of the ramp. Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Denied Reason: Date Completed : 7/4/2024 9:58:21 PM First plumbing Review: 1). Plan page M1.0:Relocated Gas water heater missing combustion air method. Add combustion air method in accordance to -2018 IFGC 304 |
||
07/19/2024 | Fire New Construction | REVIEW COMPLETED | |||
06/20/2024 | PDSD Application Completeness | REVIEW COMPLETED |