Permit Number: TC-COM-0624-01169
Parcel: 11706187E

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0624-01169
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2024 Site Zoning APPROVED
07/24/2024 Water - PDSD APPROVED
07/24/2024 Site Engineering NOT REQUIRED
07/24/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
07/05/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT 1. General: At least 5% of the dining surfaces are required to have mobility features. Provide calculations of the required
amount of accessible seating and indicate the locations including the bar. Additionally, ensure that surfaces are
properly dispersed throughout the structure. Section 226.1 and 226.2 of the 2010 ADAAG.
2. General: The plans indicate the installation of a ramp. Provide a detailed section drawing of the ramp.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 7/4/2024 9:58:21 PM
First plumbing Review:
1). Plan page M1.0:Relocated Gas water heater missing combustion air method. Add combustion air method in accordance
to -2018 IFGC 304
07/19/2024 Fire New Construction REVIEW COMPLETED
06/20/2024 PDSD Application Completeness REVIEW COMPLETED