| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/17/2024 | Commercial Electrical | APPROVED | |||
| 07/26/2024 | Commercial Structural | APPROVED | |||
| 07/15/2024 | Site Zoning | APPROVED | |||
| 07/24/2024 | Site Engineering | NOT REQUIRED | |||
| 07/26/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/23/2024 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Show the complete specifications for each air conditioner system, including the SEER2 for each system, and the heating capacity, Reference: Section R103.2, IECC 2018. 2. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections R302.2, R403.7, and R503.1.2, IECC 2018 as amended by the City of Tucson. 3. Provide a programmable thermostat for each air handler that complies with the requirements of Section R403.1.1, IECC 2018. 4. Provide mechanical ventilation for the apartment. Reference: Section R403.6, IECC 2018. |
||
| 07/23/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Specify that all proposed plumbing fixtures shall be listed by a third-party certification agency as complying with the relevant standards. Reference: Section 303.4, IPC 2018 | ||
| 06/21/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 06/20/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |