Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.2
Permit Number - TC-COM-0624-01162
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/16/2024 | Commercial Building | APPROVED | |||
08/15/2024 | Commercial Plumbing | APPROVED | |||
08/13/2024 | Site Zoning | APPROVED | |||
08/16/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
08/15/2024 | Commercial Mechanical | REQUIRES RESUBMIT | The submitted summary load calculation does not show that the heat and moisture from the dishwashing machine has been included in the HVAC load calculations. [Initial comment: Show that the heat and moisture loads from the proposed dishwashing machine are included in the HVAC load calculations for the space or install a Type II hood over the dishwashing machine. Reference: Section 507.3, IMC 2018.] | ||
07/31/2024 | PDSD Application Completeness | REVIEW COMPLETED |