Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0624-01162
Parcel: 117110170

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-0624-01162
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/16/2024 Commercial Building APPROVED
08/15/2024 Commercial Plumbing APPROVED
08/13/2024 Site Zoning APPROVED
08/16/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
08/15/2024 Commercial Mechanical REQUIRES RESUBMIT The submitted summary load calculation does not show that the heat and moisture from the dishwashing machine has been included in the HVAC load calculations. [Initial comment: Show that the heat and moisture loads from the proposed dishwashing machine are included in the HVAC load calculations for the space or install a Type II hood over the dishwashing machine. Reference: Section 507.3, IMC 2018.]
07/31/2024 PDSD Application Completeness REVIEW COMPLETED