Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0624-01161
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/17/2024 | Commercial Electrical | APPROVED | |||
07/23/2024 | Commercial Mechanical | APPROVED | |||
07/24/2024 | Commercial Structural | APPROVED | |||
07/12/2024 | Site Zoning | APPROVED | |||
07/23/2024 | Water - PDSD | APPROVED | |||
07/24/2024 | Site Engineering | NOT REQUIRED | |||
07/25/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
07/23/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Clarify the developed pipe lengths for gas risers shown on sheet P1.1. The riser detail shows one riser with a load of 832 CFH and a maximum developed length of 145 feet. One P1.0 that riser is noted as having a load of 832 CFH but a developed length of 125 feet. Similarly, the riser with 977 CFH and a developed length of 42 feet on P1.1 has a developed length of 40 feet. Reference: Sections 402.1 and 402.3, IFGC 2018. | ||
07/25/2024 | Fire New Construction | REVIEW COMPLETED | |||
06/18/2024 | PDSD Application Completeness | REVIEW COMPLETED |