Permit Number: TC-COM-0624-01161
Parcel: 110113620

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0624-01161
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2024 Commercial Electrical APPROVED
07/23/2024 Commercial Mechanical APPROVED
07/24/2024 Commercial Structural APPROVED
07/12/2024 Site Zoning APPROVED
07/23/2024 Water - PDSD APPROVED
07/24/2024 Site Engineering NOT REQUIRED
07/25/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
07/23/2024 Commercial Plumbing REQUIRES RESUBMIT Clarify the developed pipe lengths for gas risers shown on sheet P1.1. The riser detail shows one riser with a load of 832 CFH and a maximum developed length of 145 feet. One P1.0 that riser is noted as having a load of 832 CFH but a developed length of 125 feet. Similarly, the riser with 977 CFH and a developed length of 42 feet on P1.1 has a developed length of 40 feet. Reference: Sections 402.1 and 402.3, IFGC 2018.
07/25/2024 Fire New Construction REVIEW COMPLETED
06/18/2024 PDSD Application Completeness REVIEW COMPLETED