Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0624-01160
Parcel: 131100330

Address:
5502 E 22ND ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-0624-01160
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2024 Commercial Plumbing APPROVED
07/30/2024 Site Zoning APPROVED
08/02/2024 Site Engineering NOT REQUIRED
08/08/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/29/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.
1 Provide electrical plans calculations and designed, sealed by an Electrical Engineer registered in the State of Arizona.
A Registered Electrical Engineer is
required when electrical designs exceed 400 amps, and where the available fault current at
any new piece of equipment exceeds 22,000 amps, or for hazardous locations, hospitals or
buildings with operating rooms.
Reference; 2017 NEC arts 514 and 515, City of Tucson Commercial Plan Submittal Requirements.
08/05/2024 Commercial Structural REQUIRES RESUBMIT Indicate the Pipe grade and thickness, the size width or diameter of the foundation and the strength of Concrete fill. IBC 107.2.1
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
08/08/2024 Fire New Construction REVIEW COMPLETED -Contact Inspector Jesus Silva for inspections and additional permitting.
Jesus.Silva@tucsonaz.gov
cell 5204199177
desk 5208377094
-Separate permit required from TFD.
Construction permit and operational permit for LPG. Contact Jesus Silva.
07/16/2024 PDSD Application Completeness Express REVIEW COMPLETED