Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3
Permit Number - TC-COM-0624-01158
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/24/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
07/24/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Please provide more detail as to the scope of work. a. Ratings and type of service equipment. Multi-meter pack, amperage, is it a ‘Like for Like’ repair, etc. b. Any other units affected or disconnected by the utility that are part of this multi-meter pack that will also require reconnecting will need to be identified in this permit for Clearance purposes, if applicable. c. The site plan is not legible. d. Photographs submitted of the equipment requiring repair is helpful. Ref; 2018 IBC section 107.2.1, 2017 NEC |
||