Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.5

Permit Number - TC-COM-0624-01143
Review Name: COMMERCIAL REVIEW - LIMITED v.5
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
10/29/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

The original plan review comments #1 and #4 were not completely addressed . There was no written electrical review response located in the resubmittal as requested.

Provide overcurrent protection for the secondary transformer feeder and new panel ‘L’. NEC art 240.4, 240.21, 450.3, 408.36(B). Because of the location of the Transformer ‘TR-30’, NEC 408.36(B) would apply.

4. Provide complete compliance with the 2018 IECC for lighting and lighting controls. The lighting Comcheck certificate is not filled in completely. Are the office luminaires existing to remain? If yes, please indicate this in the lighting plan.

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC.
10/28/2024 Addressing Validation REVIEW COMPLETED
10/28/2024 PDSD Application Completeness REVIEW COMPLETED