Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.3

Permit Number - TC-COM-0624-01143
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/20/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
09/20/2024 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter to address each of the comments indicating how the Building Review comments were addressed. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.
1. Please submit a complete set of construction drawings with the next submittal. The current submittal only contains 5 Architectural sheets, please submit all the sheets listed in the Sheet Index. IBC 107.2.1


Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
09/20/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response. 1. There was no written response submitted addressing the previous electrical review comments. 2. There were no electrical plans submitted or revised electrical plans submitted. Ref; 2018 IBC section 107.2.1, 2017 NEC
09/09/2024 PDSD Application Completeness REVIEW COMPLETED