Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0624-01143
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/02/2024 Commercial Mechanical APPROVED
06/20/2024 Site Zoning APPROVED
06/25/2024 Site Engineering NOT REQUIRED
07/01/2024 Water - PDSD NOT REQUIRED
07/02/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
06/27/2024 Commercial Building REQUIRES RESUBMIT Please submit your revised documents, cloud and delta all changes and provide a letter with a written response letter to address each of the comments indicating how the Building Review comments were addressed. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.
Sheet T1: Please update the applicable codes to include the 2018 International Existing Building Code (IEBC) and the 2009 ICC A117.1 Accessibility Code (by reference) IBC 107.2.1
Sheet T1: Please amend plans to provide a plumbing fixture analysis - IBC 2902.1, IBC Table 2902.1 and provide the minimum number of required plumbing fixtures. Alternatively, indicate the distance to the nearest accessible toilet facilities and locate it on the site plan. IBC 107.2.1
Sheet T1: Related to the above comment 2 above, provide the required directional signage indicating the route to the required public toilet facilities shall be posted, such that the sign can be readily seen from the main entrance to the building or tenant space.
Sheet T1: Please amend plans to provide signs for accessible toilet facilities in accordance with IBC Section 1111

Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
07/01/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Provide overcurrent protection for the secondary transformer feeder and new panel ‘L’. NEC art 240.4, 240.21, 450.3, 408.36(B). Because of the location of the Transformer ‘TR-30’, NEC 408.36(B) would apply.

2 Provide a feeder schedule that correlates with the electrical line diagram feeders.

3 Provide a grounding detail for the transformer.

4 Provide complete compliance with the 2018 IECC for lighting and lighting controls.

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC.
07/02/2024 Commercial Plumbing REQUIRES RESUBMIT Please submit your revised documents, cloud and delta all changes and provide a letter with a written response letter to address each of the comments indicating how the Review comments were addressed.
Sheet P2: Please amend plans to provide a minimum plumbing fixture analysis - IBC 2902.1, IBC Table 2902.1, IPC 403.
Sheet P2: Indicate the location of the required plumbing fixtures indicated in plumbing fixture analysis. IBC 107.2.1If remote, provide the distance and show location on site plan. IBC 107.2.1
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
06/21/2024 Fire New Construction REVIEW COMPLETED
06/14/2024 PDSD Application Completeness REVIEW COMPLETED