Permit Number: TC-COM-0624-01121
Parcel: 13506136H

Address:
2550 S KOLB RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0624-01121
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/26/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/26/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements.

2. Provide site lighting plans with the following information on the plans;

(a) Provide a complete luminaire schedule.

(b) Full compliance with sections 104.2.1(1), (2), (3).

3 See table 401.1, Include parcel size, lighting area and option, and indicate this information in the lighting site plan.

4 402.1 (light source color temperature requirements, 3500K), shielding requirements, etc .

5 Provide calcs for total lumens allowed and total lumens proposed per acre for Full Cut Off and Unshielded per table 401.1.Must include existing to remain lighting.

6 Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

7 Specify any exceptions used.

8 Provide Curfew lighting controls If applicable Per section 403.

9 Provide complete compliance with the 2018 IECC for the interior and exterior lighting where applicable.

Do not confuse the Outdoor Lighting Code with the IECC.

10 Please provide more detail as to the as to the exact scope of work both interior and exterior.

11 In order to apply permit fees. Rather than enter the number of luminaires being retrofitted in the fee calculator. It would be reasonable to enter the number of branch circuits associated with the luminaires. Please provide this information on the plans.

Ref; 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC), 2018 IBC sec 107.2.1. 2018 IECC.