Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0624-01119
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/16/2024 | Commercial Structural | APPROVED | |||
| 07/16/2024 | Site Engineering | APPROVED | |||
| 07/08/2024 | Site Zoning | APPROVED | |||
| 07/16/2024 | Commercial Mechanical | NOT REQUIRED | |||
| 07/16/2024 | Commercial Plumbing | NOT REQUIRED | |||
| 07/16/2024 | Water - PDSD | NOT REQUIRED | |||
| 07/16/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/15/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Show the location of the sub-panel to be replaced. Be advised that it cannot be located in a closet or bathroom. NEC art 240.24(D)(E). 2 This multi- family building is considered a commercial project. Remove all references to the IRC and revise to the 2017 NEC. 3 Provide combination type Arc-Fault protection on all branch circuits as required per NEC art 210.12. 4 Verify compliance with the 2012 City of Tucson Outdoor Lighting Code for the exterior lighting. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code. |
||
| 06/13/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 06/13/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |