Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0624-01119
Parcel: 113072500

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0624-01119
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2024 Commercial Structural APPROVED
07/16/2024 Site Engineering APPROVED
07/08/2024 Site Zoning APPROVED
07/16/2024 Commercial Mechanical NOT REQUIRED
07/16/2024 Commercial Plumbing NOT REQUIRED
07/16/2024 Water - PDSD NOT REQUIRED
07/16/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/15/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Show the location of the sub-panel to be replaced. Be advised that it cannot be located in a closet or bathroom. NEC art 240.24(D)(E).

2 This multi- family building is considered a commercial project. Remove all references to the IRC and revise to the 2017 NEC.

3 Provide combination type Arc-Fault protection on all branch circuits as required per NEC art 210.12.

4 Verify compliance with the 2012 City of Tucson Outdoor Lighting Code for the exterior lighting.

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code.
06/13/2024 Fire New Construction REVIEW COMPLETED
06/13/2024 PDSD Application Completeness Express REVIEW COMPLETED