Permit Number: TC-COM-0624-01117
Parcel: 10605001B

Address:
3959 N ORACLE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0624-01117
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
07/15/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 The rating of the AC electrical system associated with this project exceeds 400 amps the AIC ratings of the electrical switchgear and associated equipment downstream is not shown and there appears to be more than one electrical service associated with this project.

2 The full scope of electrical work associated with the Renovation is not shown. The panels schedules appear to indicate new or revised branch circuits for power and lighting. There was no electrical site or power and lighting plans submitted. This facility also qualifies as a hazardous facility per NEC art 511.

Please provide complete sealed electrical plans. Electrical design and calculations performed by an Arizona registered Electrical Engineer who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work.

Reference: 2018 IBC section 107, 2017 NEC, 2018 IECC, 2012 City of Tucson Outdoor Lighting Code, Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304". City of Tucson Commercial Plan Submittal Requirements.
07/18/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Revise the sequence of operation for the restroom exhaust fans (EF-1, EF-2, EF-4, and EF-5) so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2018.
2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the new HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
07/18/2024 Commercial Plumbing REQUIRES RESUBMIT 1. For the use of PEX tubing, provide a branch tube sizing chart showing the correct size of PEX tubing to be used as a substitute for the copper pipe shown on the drawings. Reference: Sections 303.2 and 604.3, IPC 2018.
2. Provide metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. For accessibility, verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
3. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
07/19/2024 Commercial Structural REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter to address each of the comments indicating how the Building Review comments were addressed. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.
1. Please submit structural calculations prepared by an Arizona licensed registrant with next submittal. IBC 107.2.7
2. Please amend plans to name the registered design professional in responsible charge is named, with contact info. IBC 107.3.4

Please contact me if you have any questions about these comments.

Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
07/16/2024 Site Engineering REQUIRES RESUBMIT TD-DEV-0524-00161 must be approved prior to building permit approval.

Mike Ortiz
michael.ortiz@tucsonaz.gov
07/15/2024 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Fernando Garcia
Planning & Development Services Department – Zoning Review Section

PROJECT:
TC-COM-0624-01117 – Commercial Building
3959 N Oracle Rd, Tucson, AZ 85705
Plan Review (1st Review)

TRANSMITTAL DATE: July 15, 2024

1. (Comment) This parcel is located in an I-1 zone. The uses of this commercial construction project are classified as “trade service and repair, major” and “commercial storage”. These uses are permitted in an I-1 zone.

2. (Comment) Zoning review approval of this commercial construction permit is contingent upon approval of a development package for the site. Zoning review approval of this permit will be held until associated development package permit TD-DEV-0524-00161 is approved.

Any changes made to TD-DEV-0524-00161 will need to be reflected on resubmitted plans for this permit prior to its approval.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Resubmitted plans per approved development package TD-DEV-0524-00161.

If you have any questions about this transmittal, please contact Fernando L. Garcia at fernando.garcia2@tucsonaz.gov.
07/18/2024 Water - PDSD REQUIRES RESUBMIT Show the location and size of the existing water meter, backflow preventer, and the water service pipe on a site plan. Provide the total water demand that will be served by the water meter. Reference: Section 107.2.1, IBC 2018.
07/16/2024 Fire New Construction REVIEW COMPLETED
06/13/2024 PDSD Application Completeness REVIEW COMPLETED