Permit Number: TC-COM-0624-01115
Parcel: 10713188A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0624-01115
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2024 Commercial Structural APPROVED
08/23/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
08/22/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Comment not addressed. [Initial comment: Assuming that the rooftop heat pumps are new work, provide mechanical ventilation for each apartment. Reference: Section R403.6 (N1103.5), IECC (IRC) 2018.]
2. Clarify the status of the rooftop units and their energy efficiencies. The proposed equipment schedules show different SEER values than the HVAC Equipment boxed note and in one area the 2-ton unit is existing and it is new in another note. The 3-ton unit is similarly new in one place and existing in another place. [Initial comment: Assuming that the rooftop heat pumps are new work, show the complete specifications for each heat pump system, including the SEER and HSPF for each unit, any supplemental heaters, and the air leakage rating of the air handler (ASHRAE Standard 193). Reference: Sections R103.2, R403.7 and R501.5, IECC 2018.]
07/26/2024 PDSD Application Completeness REVIEW COMPLETED