Permit Number: TC-COM-0624-01115
Parcel: 10713188A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0624-01115
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/15/2024 Commercial Electrical APPROVED
07/16/2024 Site Engineering APPROVED
07/08/2024 Site Zoning APPROVED
07/18/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
07/18/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Clarify what is existing and what is being added to the building as part of this activity. Reference: Section 107.2.1, IBC 2018.
3. Assuming that the rooftop heat pumps are new work, provide a programmable thermostat for each heat pump that complies with the requirements of Section R403.1.1, IECC 2018.
4. Assuming that the rooftop heat pumps are new work, provide mechanical ventilation for each apartment. Reference: Section R403.6 (N1103.5), IECC (IRC) 2018
5. Assuming that the rooftop heat pumps are new work, show the complete specifications for each heat pump system, including the SEER and HSPF for each unit, any supplemental heaters, and the air leakage rating of the air handler (ASHRAE Standard 193). Reference: Sections R103.2, R403.7 and R501.5, IECC 2018.
07/18/2024 Commercial Structural REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter to address each of the comments indicating how the Building Review comments were addressed. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.
1. Please indicate the type of roof that is to be repaired, and ensure all references are consistent. IBC 107.2.1 For example, the north and south elevations indicate shingles and the east and west elevations indicate built up roofing.
2. Please amend plans to specify how the repairs are to be made to the roof and facia. IBC 107.2.1 For example, Like for Like or ?
3. Please amend plan to indicate the existing and new walls IBC 107.2.1
Please contact me if you have any questions about these comments.


Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
06/13/2024 Fire New Construction REVIEW COMPLETED
06/13/2024 PDSD Application Completeness REVIEW COMPLETED