Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0624-01113
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/16/2024 | Commercial Structural | APPROVED | |||
| 07/02/2024 | Site Zoning | APPROVED | |||
| 07/16/2024 | Commercial Mechanical | NOT REQUIRED | |||
| 07/08/2024 | Site Engineering | NOT REQUIRED | |||
| 07/16/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/26/2024 | Commercial Electrical | REQUIRES RESUBMIT | Permit Review TC-COM-0624-01113 (1705 W SPEEDWAY BL TUCSON, AZ 85745) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Provide PV interconnection in compliance with NEC 705.12. See NEC 705.12(B)(2)(1) a-b & 705.12(B)(2)(2). a.) Show the OCPD on the load side of the feeder for Distribution Panels A and B Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 06/11/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 06/11/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |