Permit Number: TC-COM-0624-01097
Parcel: 121060070

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0624-01097
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/24/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/24/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 7/24/2024 12:49:40 PM
1. (RESOLVED) - General - Provide Ventilation Calculation/Schedule - 2018 IMC section 403 Table 403.3.1.1 -
ASHRAE 62.1.
2. (UNRESOLVED) - General - Provide COMcheck Mechanical Compliance Certificate - 2015 IECC Section C403.3.2
HVAC equipment performance requirements.
i. Submitted COMcheck Mechanical Compliance Certificate does not match for RTUs #1 thru #9. RTU. All (9) unit
Tags on Plan Sheet are 5 ton units with 2000 CFM. COMcheck states (8) 10 ton units and (1) 3 ton unit.
Confirm unit specifications and make corrections. - 2015 IECC Section C403.3.2 HVAC equipment performance requirements.
3. (UNRESOLVED) - General - Provide Energy Heat Load Calculations - 2015 IECC Section C403.2.1 Calculation of heating and cooling loads.
i. Heat Loads not submitted for review. - 2015 IECC Section C403.2.1 Calculation of heating and cooling loads.
4. (UNRESOLVED) - Plan Sheet M1 - RTU identification, adjacent to each RTU does not match the RTU Heating and Cooling Schedule (CFM)- 2018 IECC Section C103.2Information on construction documents. - 2018 IBC – Section [A]107.2.1Information on construction documents
i. Plan Sheet M-1.1A - The RTU Heating and Cooling Schedule states (8) 10 ton units with 4000 CFM of supply
air and (1) 5 ton unit with 2000 CFM of supply air. This does not match the Unit Tags on Plan Sheet M-1.0. Confirm unit sizes and make corrections to the construction documents.
07/19/2024 PDSD Application Completeness Express REVIEW COMPLETED