Permit Number: TC-COM-0624-01086
Parcel: 127022330

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.4

Permit Number - TC-COM-0624-01086
Review Name: COMMERCIAL REVIEW - LIMITED v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/28/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/18/2025 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Building Review comments were addressed. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Plans were incomplete and additional comments may result after original comments are addressed.
10. NEW COMMENT: Please apply for an additional permit so each S-1 Shade Canopy has an individual permit. The same plans can be used for both permits: however please use Building A and Building B for identification on the site plan and all plan view drawings.IBC 107.2.1
11. NEW COMMENT: Type of construction is listed as II-B and includes note fire protection note stating ‘NOT REQUIRED FOR OPEN METAL STRUCTURES’. IBC Table 602 requires a 2-hour fire-resistive rating when the structure is less than 5 feet from the property line. Since there is no exterior wall, then the area under the canopy but next to the property line is considered an opening, and IBC Table 705.8 does not allow any openings within 3 feet of the property line. Please amend the drawings to increase the fire setback distance to meet the requirements of Tables 602 and 705.8 , or provide the required fire-resistive rated exterior wall for the setback in table 602. IBC 107.2.1
12. NEW COMMENT: Provide the Fire Separation Distance from the Western property line to the edge of the roof for Building A. IBC 107.2.1 This will determine the fire-resistive rating required for construction. IBC 107.2.1 & IBC Table 602.
13. NEW COMMENT: Please indicate if the smaller, Building B, 20’-0” X 53’-8” is connected to the existing building or is free-standing. Please provide calculations and design for smaller Shade Canopy. If connected to the existing building, please provide connection details and drawings. IBC 107.2.1
14. NEW COMMENT: Please amend the structural calculations to include the wind speed and risk category used in the design. IBC 107.2.7
15. NEW COMMENT: Please amend the structural calculations to include lateral analysis for both structures. IBC 107.2.1
16. NEW COMMENT: lease provide the special inspection certificate with Part A, and Part B, completed with next submittal. IBC 107.2.1
https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf

Please contact me if you have any questions about these comments.
Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov
03/18/2025 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0624-01086 (5134 E SPEEDWAY BL TUCSON, AZ 85712)

1. Submit catalogue or specification sheets of all proposed new outdoor lighting fixtures illustrating the type of fixture, color temperature, lumens rating and whether full cut-off or unshielded.
03/28/2025 Site Engineering REQUIRES RESUBMIT TC-COM-0624-01086
5134 E SPEEDWAY BL

Site engineering comments are as follows:
1. The associated development package, TD-DEV-0225-00059, must be approved by all reviewers prior to the approval of this permit submission. UDC Article 3.3.3.7.a
Ryan Insalaco – ryan.insalaco@tucsonaz.gov
03/05/2025 Site Zoning REQUIRES RESUBMIT FROM: Ramiro Olivarez
PDSD Zoning Review Section
PROJECT: TC-COM-0624-01086 | DP Ref. TD-DEV-0225-00059| T22DV00680
5134 E SPEEDWAY BL. - C-2 A Major Automotive Service and Repair; Shade Awning (2nd Review)

TRANSMITTAL DATE: ‎March 05, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. The site is in the C-2 zone (UDC 4.7.21). A Major Automotive Service and Repair use is permitted in the C-2 zone, subject to use-specific standard 4.9.13.E.1.

1. Zoning has reviewed the building permit for compliance with development package (DP) TD-DEV-0225-00059 and although it appears that the building plan is in compliance, until the DP is approved by all review agencies Zoning cannot approve this plan.


If you have any questions about this transmittal, please contact Ramiro Olivarez at Ramiro.Olivarez@tucsonaz.gov
03/04/2025 PDSD Application Completeness Express REVIEW COMPLETED