Permit Number: TC-COM-0624-01078
Parcel: 12212026C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0624-01078
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/01/2025 Site Zoning Standard APPROVED
08/05/2025 Water - PDSD Standard APPROVED
08/06/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/06/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.

1. Sheet S-100; Please update drawing to include a seal with signature, and date signed by an Arizona licensed registrant with next submittal. IBC 107.2.1

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
08/05/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
2. Provide cleanouts for all horizontal drains; the cleanouts shall not be located greater than 100-feet apart, measured along the developed pipe length from the upstream entrance of the cleanout. Provide an additional cleanout for each 40-foot section of drains having a change of direction greater than 45 degrees Reference: Sections 708.1.1 and 708.1.4, IPC 2018.
07/15/2025 PDSD Application Completeness Express REVIEW COMPLETED