Permit Number: TC-COM-0624-01077
Parcel: 13323190A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0624-01077
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/03/2024 Commercial Electrical APPROVED
07/10/2024 Commercial Mechanical APPROVED
07/10/2024 Commercial Structural APPROVED
06/27/2024 Site Zoning APPROVED
07/02/2024 Site Engineering NOT REQUIRED
07/10/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/10/2024 Commercial Plumbing REQUIRES RESUBMIT Revise the waste isometric to show the drainage fitting for the water closet installed to guide sewage in the direction of flow. Reference: Section 706.3, IPC 2018.
07/10/2024 Water - PDSD REQUIRES RESUBMIT Revise the water calculations to include all of the plumbing fixtures (e.g., 2 additional water closets, an additional lavatory , the service sink, and a drinking fountain) and appliances that are served by the existing water meter. If the demand exceeds 20 GPM, install a larger water meter.
06/09/2024 Fire New Construction REVIEW COMPLETED
06/06/2024 PDSD Application Completeness Express REVIEW COMPLETED