Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0624-01077
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/03/2024 | Commercial Electrical | APPROVED | |||
07/10/2024 | Commercial Mechanical | APPROVED | |||
07/10/2024 | Commercial Structural | APPROVED | |||
06/27/2024 | Site Zoning | APPROVED | |||
07/02/2024 | Site Engineering | NOT REQUIRED | |||
07/10/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
07/10/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Revise the waste isometric to show the drainage fitting for the water closet installed to guide sewage in the direction of flow. Reference: Section 706.3, IPC 2018. | ||
07/10/2024 | Water - PDSD | REQUIRES RESUBMIT | Revise the water calculations to include all of the plumbing fixtures (e.g., 2 additional water closets, an additional lavatory , the service sink, and a drinking fountain) and appliances that are served by the existing water meter. If the demand exceeds 20 GPM, install a larger water meter. | ||
06/09/2024 | Fire New Construction | REVIEW COMPLETED | |||
06/06/2024 | PDSD Application Completeness | REVIEW COMPLETED |