Permit Number: TC-COM-0624-01061
Parcel: 14043013F

Review Status: Requires Resubmit

Review Details: RESTAMP - COMMERCIAL v.1

Permit Number - TC-COM-0624-01061
Review Name: RESTAMP - COMMERCIAL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2024 Commercial Electrical APPROVED
08/15/2024 Site Zoning APPROVED
08/15/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/15/2024 Commercial Plumbing REQUIRES RESUBMIT Water downstream of the backflow preventer serving the car wash equipment is non-potable. Provide signage and pipe labeling identifying the non-potable water piping downstream of the backflow preventer. Reference: Section 608.9, IPC 2018.
08/15/2024 Water - PDSD REQUIRES RESUBMIT Show the location and size of the reduced pressure zone backflow assembly that will be protecting the site water distribution from the car wash equipment. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf