Review Status: Requires Resubmit
Review Details: RESTAMP - COMMERCIAL v.1
Permit Number - TC-COM-0624-01061
Review Name: RESTAMP - COMMERCIAL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/15/2024 | Commercial Electrical | APPROVED | |||
08/15/2024 | Site Zoning | APPROVED | |||
08/15/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
08/15/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Water downstream of the backflow preventer serving the car wash equipment is non-potable. Provide signage and pipe labeling identifying the non-potable water piping downstream of the backflow preventer. Reference: Section 608.9, IPC 2018. | ||
08/15/2024 | Water - PDSD | REQUIRES RESUBMIT | Show the location and size of the reduced pressure zone backflow assembly that will be protecting the site water distribution from the car wash equipment. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf |