Permit Number: TC-COM-0623-01623
Parcel: 12801005H

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0623-01623
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/06/2023 Site Zoning APPROVED
07/31/2023 Water - PDSD APPROVED
07/10/2023 Site Engineering NOT REQUIRED
07/31/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
07/24/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 7/24/2023 8:48:53 AM
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall
not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 7/12/2023 1:38:17 PM
1. Ensure that the tenant separation wall maintains it required fire resistance rating.



Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Denied
Reason:
Date Completed : 7/3/2023 1:32:59 PM
1. Smoke detectors shall be installed in return air systems with a design capacity greater than 2,000 cfm (IMC2018,606.2.1)
2. The duct smoke detectors shall be tied into the building fire alarm



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 7/11/2023 11:36:09 AM
Electrical Review JD Sports
By: Ron Ross PE
E-111 ELECTRICAL POWER PLAN: Could not locate Keynote 13.
E-112 ELECTRICAL POWER PLAN: Keynote 4 seems to be in the wrong location.


Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 7/15/2023 12:07:39 PM
First Plumbing Review:
1). Lavatory faucet on plan page P-001 needs to be an automatic type. Tucson Amendment 412.11, 419.6
2). Lavatory faucet on plan page P-001 needs an ASSE 1070 mixing valve - IPC 419.5
3). Floor drain on plan page P-001 needs trap primer or trap guard 1002.4.1
07/20/2023 Fire New Construction REVIEW COMPLETED
06/30/2023 PDSD Application Completeness REVIEW COMPLETED