Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0623-01617
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/04/2023 | Commercial Structural | APPROVED | |||
| 07/06/2023 | Site Zoning | APPROVED | |||
| 08/04/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/01/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. Ref; Electrical Line Diagram. The MDP is fed with a 3- phase feeder including a Neutral. The Generator feeder is 3 #2 and a #2 ground. No Neutral? Please clarify. The plan reviewer tried to contact the Registrant of record to get clarification but the Registrant was un- available. Ref; 2018 IBC section 107.2.1, 2017 NEC |
||
| 07/16/2023 | Fire New Construction | REVIEW COMPLETED | |||
| 06/30/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |