Permit Number: TC-COM-0623-01606
Parcel: 133165770

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0623-01606
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2023 Site Zoning APPROVED
07/27/2023 Water - PDSD APPROVED
07/10/2023 Site Engineering NOT REQUIRED
07/27/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/10/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0623-01606

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


Structural(S) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 7/7/2023 7:49:49 PM
1. Sheet T-1.0 – Provide applicable codes for City of Tucson IBC Local Amendments.
2. Structural plans missing.


Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 7/7/2023 7:51:32 PM
1. Sheet T-1.0 – Provide applicable codes for City of Tucson IBC Local Amendments. “2021”
City of Tucson IBC Local Amendments
• Amendments to the 2018 International Building Code
• Amendments to the 2018 International Existing Building Code
• Amendments to the 2018 International Energy Conservation Code
• Amendments to the 2018 International Fuel Gas Code
• Amendments to the 2018 International Mechanical Code
• Amendments to the 2018 International Plumbing Code
• Amendments to the 2018 International Residential Code
• Amendments to the 2018 International Swimming Pool & Spa Code
• Amendments to the 2017 National Electrical Code
• Amendments to the 2018 International Fire Code
• City of Tucson/Pima County Outdoor Lighting Code
• Arizona Administrative Code Title 18 Chapter 5 for public and semi-public swimming pools
• ICC A117.1 - 2009 Accessible and Usable Buildings and Facilities (by reference)
Adopting Local Amendments to the Building Code is authorized by Ordinance #11590.
2. Sheet A-0.0 – Provide required plumbing fixture calculations accordance with 2018 IBC section 2902 minimum plumbing facilities. Show required and provided water closets, lavatories, drinking fountains and service sink in this new facility.
3. Sheet A-0.0 – Office 108 is existing through the kitchen and storage. 2018 IBC Section 1016.2 item 5 states “Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes.”
4. Provide overall floor plan showing the adjacent occupancy classification. Is it a business occupant next to this new assembly occupancy?
5. Provide demolition/existing floor plan. Provide plan of empty shell space. Sheet T-1.0 site plan key plan photo is misleading showing existing building that doesn’t match this new building profile.
6. Sheet A-1.0/A-1.0A – Occupancy separating demising wall at grid 3 is not providing fire rated wall UL listed assembly. 2018 IBC Table 508.4 i.e. required separation of occupancies. Is the adjacent a business occupancy? Then A/B separation shows 1 hour minimum in sprinkler building.


Mechanical(M) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 7/7/2023 7:50:24 PM
1. Sheet T-1.0 – Provide applicable codes for City of Tucson IBC Local Amendments.
2. Sheet M-2.1 – Intake of existing roof top unit (RTU-2) appears within the 10’-0” kitchen exhaust fan. 2018 IMC section 401.4 intake opening location states “2. Mechanical and gravity outdoor air intake openings shall be located not less than 10 feet horizontally from any hazardous or noxious contaminant source,…”


Electrical(E) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 7/7/2023 7:50:43 PM
1. Sheet T-1.0 – Provide applicable codes for City of Tucson IBC Local Amendments.


Plumbing(P) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 7/7/2023 7:50:05 PM
1. Sheet T-1.0 – Provide applicable codes for City of Tucson IBC Local Amendments.
2. Sheet P1.0/P-3.0 note 7 states existing grease interceptor and verify in field. City of Tucson Amendments to the 2018 International Plumbing Code section 1003.3 provides Gravity Grease Interceptor table minimum size is 300 gallon. Is “GB-250” 300 gallon? Provide DFU defined in Pima County Industrial Wastewater Ordinance 13.36.420. Fixtgures to be connected to a grease interceptor located within the kitchen area should comply with City of Tucson Amendments to the 2018 International Plumbing Code.
07/20/2023 Fire New Construction REQUIRES RESUBMIT -Code analysis. We are currently in the 2018 I-codes. 2018 IFC.
-Deferred submittals. Include dedicated function fire alarm for fire sprinkler, hood and CO2 gas detection monitoring (if applicable).
-Indicate if bulk CO2 for beverage dispensing will be used. If so, gas detection alarm shall be installed per IFC 5307.3
-Exit door D1.1 shall have panic hardware per IFC 1010.1.10. This also applies to the gate from the patio unless no exiting hardware is being used.

john.vincent@tucsonaz.gov
5203495581
06/30/2023 PDSD Application Completeness Express REVIEW COMPLETED