Permit Number: TC-COM-0623-01605
Parcel: 10511061P

Address:
4510 N ORACLE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0623-01605
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2023 Site Zoning APPROVED
07/27/2023 Water - PDSD APPROVED
07/10/2023 Site Engineering NOT REQUIRED
07/27/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
07/17/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0623-01605

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Conditinally Approved
Reason:
Date Completed : 7/17/2023 10:22:26 AM
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.


Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 7/7/2023 2:07:33 PM
1. General: The existing structure currently exceeds the maximum allowable area per Table 506.2. However, it is unknown if any area increases have been applied upon the issuance of the Certificate of Occupancy. Provide additional clarification.
2. Sheet G0.1: The occupant load calculation indicated areas as "area not part of this occupancy", however, it's included in the occupancy area with no load calculated. Provide space occupant load calculation that includes all areas within the occupancy in accordance with Table 1004.5.


Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Approved
Reason:
Date Completed : 7/1/2023 7:58:16 PM
No mechanical being done per engineer existing mechanical to remain


Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 7/7/2023 8:50:00 AM
Electrical Review of Curacao
By: Ron Ross PE
E3.1: Should remove the 12 AWG size from the 30A Branch Circuit Rating column.


Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 7/13/2023 9:04:25 PM
07/19/2023 Fire New Construction REVIEW COMPLETED Separate permits required for modifications/additions to:
* fire sprinkler
* fire alarm
06/30/2023 PDSD Application Completeness REVIEW COMPLETED