Permit Number: TC-COM-0623-01605
Parcel: 10511061P

Address:
4510 N ORACLE RD

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0623-01605
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
08/14/2023 Bldg Permits - Post Review REVIEW COMPLETED
08/14/2023 External Reviewers - SAFEBuilt REVIEW COMPLETED Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 7/17/2023 10:22:26 AM
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 8/11/2023 7:26:51 PM



Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Approved
Reason:
Date Completed : 7/1/2023 7:58:16 PM
No mechanical being done per engineer existing mechanical to remain
Approved




Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 7/7/2023 8:50:00 AM
Electrical Review of Curacao
By: Ron Ross PE
E3.1: Should remove the 12 AWG size from the 30A Branch Circuit Rating column.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 7/13/2023 9:04:25 PM
08/07/2023 PDSD Application Completeness REVIEW COMPLETED