Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0623-01601
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2023 Site Zoning APPROVED
07/27/2023 Water - PDSD APPROVED
07/10/2023 Site Engineering NOT REQUIRED
07/27/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/06/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0623-01601

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Structural(S) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 7/6/2023 5:24:01 AM
Sheet M1.0 – Detail 2/M1.0 notes “(REF. STRUCT.)” yet this structural sheet is missing. Show roof detail of how new 4 ton model with max weight of 700 lbs is supported: “Carrier, 50GCQM05, MCA 24, MOCP 30, 208/3/60, 700 LBS.”


Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 7/6/2023 5:24:39 AM
Sheet TS1 – Sprinklers in code study reference existing dry standpipes and “N/A” for wet standpipes, but sheet MP1.0 fire protection states “fire protection system is a wet pipe automatic sprinkler system.” Sheet P1 also reference “wet pipe sprinkler system.” Coordinate drawings to fix this discrepancy.


Mechanical(M) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Approved
Reason:
Date Completed : 7/6/2023 5:24:17 AM


Electrical(E) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Approved
Reason:
Date Completed : 7/6/2023 5:24:24 AM


Plumbing(P) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Approved
Reason:
Date Completed : 7/6/2023 5:24:08 AM
07/13/2023 Fire New Construction REQUIRES RESUBMIT Address SAFEBuilt comments
06/29/2023 PDSD Application Completeness Express REVIEW COMPLETED