Permit Number: TC-COM-0623-01599
Parcel: 11003093A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0623-01599
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2024 Site Engineering APPROVED
07/10/2024 Site Zoning APPROVED
08/12/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
08/12/2024 Commercial Building REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0623-01599
ADDRESS/PARCEL: (4013 E FORT LOWELL RD TUCSON, AZ 85712)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter.
COMMENTS:
1. Please locate and label the water fountain enumerated within the Development package as existing to remain as well as within your Code Analysis indicating one is required.
2. Show in your restroom the clearances complying to ICC/ANSI A117.1 section 604.3 Clearances as well as section 404 Doors. (NOTE: Ensure that the required clearances on the accessible route from the front door to the restroom complies to ICC/ANSI A117.1)
3. In the Reception, provide drawings illustrating the work surface or service counter complying to ICC/ANSI A117.1 section 902 specifically the height and width and section 306 Knee and Toe Clearances.
4. From the Scope of Work: "THE STORAGE AND POWDER ROOM AT THE REAR OF THE BUILDING WERE ADDED AHEAD OF RECEIVING A PERMIT BY THE PREVIOUS OWNER."Please submit a complete set of drawings (MEP & Architecturally) for this new Storage and Powder Room.
5. Please submit a copy of the draft for the Arizona Department of Health Services operator's license application, this will allow the city to accurately fill the Certificate of Occupancy document.
6. For due dilligence only: Please provide information what is being stored in the new storage addition.
7. Please show your occupant load calculation for each space specially the reception area and office #1. Show the layout for each room on your floor plan to see that the means of egress route is clear. NOTE: Shouldn't office #1 be an assembly space?
8. Please resubmit.