07/03/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
07/03/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.
Please provide more information describing the scope of work.
1. What is the new 200 amp service upgrading from?
2.What is the Voltage, Phase, Aic , ratings.
3. Is this a Like for Like installation? If Like for Like, same location, same size, no plan is required.
4. If new location. The site plan needs to show an address, apt or unit # if applicable. Show the building and location of the service on the building, a complete line diagram, plans sealed by a registrant registered in the State of Arizona.
Ref; 2018 IBC sections 107.2.1, 107. 107.2.6, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.