Permit Number: TC-COM-0623-01583
Parcel: 112010340

Address:
2544 E ALLEN RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0623-01583
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
07/10/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

Per the response letter. The addition information pertaining to the scope of work involves:

(a) Changing the existing service drop from Overhead to Underground.

(b) Increasing the rating of the service from 100 to 200 amps.

2. Due to these changes from the existing electrical service. This does not qualify as ‘Like for Like’. ‘Like for Like’ is Everything, (Ratings) remain the same. This would be categorized as a service upgrade and ‘Increase’ (per TEP’s terms).

3. Why the increase in amp rating? Is the load going to be affected?

4. Design and calculations will be required. Please provide a complete and sealed electrical plan(s), calculations and design by a Registrant registered in the State of Arizona.

Ref; 2018 IBC section 107.2.1, 2017 NEC.
07/05/2023 PDSD Application Completeness REVIEW COMPLETED