Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - TC-COM-0623-01577
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/03/2023 | PDSD Application Completeness | REQUIRES RESUBMIT | Please resubmit a gas piping template. Please see the below information for existing commercial gas lines. The following requirements must be shown on drawing before development services will approve and issue a permit. Drawings must have a minimum text size of 1/8” in all upper case. 1. Project Address 2. Permit Activity number 3. Company name 4. Name of person who prepared the drawing along with date drawing was prepared 5. North arrow 6. Floor plan of building showing location of the gas meter, routes of the gas piping, and the locations of the connected loads 7. Total load on the gas meter (BTUH) 8. Individual connected loads (BTUH) 9. Developed length of pipe 10. Pipe sizes 11. Location of any branch shut-off or automatic valves Sample Template: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/permits/residential-permits/sample_gas_template_0.pdf Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf |