Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0623-01575
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/03/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/03/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. Please provide an Electrical Site Plan showing the location of the temporary electrical service and Panels. Ref; ‘Temporary Power Details’ plan. Provide more detail as to the function or loads of the 400 amp ‘Panel for Temp Power’, and how it is mounted or supported. Also the load calculations for this panel shows 320 amps. Show what these loads are and provide a panel schedule. Ref; 2018 IBC section 107.2.1, 107.2.6, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
||
| 06/27/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |