Review Date Reviewer's Name Type of Review Description Status Comments
07/03/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/03/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

Please provide an Electrical Site Plan showing the location of the temporary electrical service and Panels.

Ref; ‘Temporary Power Details’ plan. Provide more detail as to the function or loads of the 400 amp ‘Panel for Temp Power’, and how it is mounted or supported. Also the load calculations for this panel shows 320 amps. Show what these loads are and provide a panel schedule.

Ref; 2018 IBC section 107.2.1, 107.2.6, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.