Permit Number: TC-COM-0623-01561
Parcel: 111083830

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0623-01561
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/07/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/07/2023 Commercial Mechanical REQUIRES RESUBMIT 1. Electrical services that are less than 150 Amps require electrical load calculations.
2. Clarify the unit to be installed. The Air Conditioning Installation Template calls for a split system heat pump (GSZM4) but the Heating/cooling load calculations specify a split system air conditioner with electric heat (GSXM4).
3. Clarify the maximum overcurrent protection. The heat pump has a maximum overcurrent protection of 30 Amps while the AC condensing unit has a maximum overcurrent protection of 25 Amps, not the 35 Amps as shown on the Air Conditioning Installation Template.
4. Verify the SEER2 (and HSPF2 if the unit is a heat pump) rating. The manufacturer shows a SEER2 range of 13.8 to 14.5 for both units. The minimum acceptable SEER2 is 14.3 for this area.
11/02/2023 PDSD Application Completeness Express REVIEW COMPLETED