Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - TC-COM-0623-01561
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/07/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/07/2023 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Electrical services that are less than 150 Amps require electrical load calculations. 2. Clarify the unit to be installed. The Air Conditioning Installation Template calls for a split system heat pump (GSZM4) but the Heating/cooling load calculations specify a split system air conditioner with electric heat (GSXM4). 3. Clarify the maximum overcurrent protection. The heat pump has a maximum overcurrent protection of 30 Amps while the AC condensing unit has a maximum overcurrent protection of 25 Amps, not the 35 Amps as shown on the Air Conditioning Installation Template. 4. Verify the SEER2 (and HSPF2 if the unit is a heat pump) rating. The manufacturer shows a SEER2 range of 13.8 to 14.5 for both units. The minimum acceptable SEER2 is 14.3 for this area. |
||