Permit Number: TC-COM-0623-01550
Parcel: 14042002A

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0623-01550
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
06/27/2023 Commercial Plumbing REQUIRES RESUBMIT 1. Provide plans sealed by an Arizona Registrant. Reference: Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Show how the water distribution piping system for the suite will be modified for the installation of the two new water heaters. Reference: Section C404.4 and C404.5, IECC 2018.
3. Clarify the existing gas service for the suite (i.e. 2 PSIG or 7” WG), the changes being made to the system, and the total gas load for the system. Reference: Section 107.2.1, IBC 2018.
4. Condensate from the combustion process shall not be discharged to the roof but shall be treated and then discharged to an approved plumbing fixture. Reference: Section 314.1, IPC 2018.
5. A temperature and pressure relief valve shall not discharge onto the roof but shall discharge to a termination point that is observable by the building occupants. Reference: Section 504.6, IPC 2108.
06/23/2023 PDSD Application Completeness REVIEW COMPLETED