Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0623-01550
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/27/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
06/27/2023 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Provide plans sealed by an Arizona Registrant. Reference: Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Show how the water distribution piping system for the suite will be modified for the installation of the two new water heaters. Reference: Section C404.4 and C404.5, IECC 2018. 3. Clarify the existing gas service for the suite (i.e. 2 PSIG or 7” WG), the changes being made to the system, and the total gas load for the system. Reference: Section 107.2.1, IBC 2018. 4. Condensate from the combustion process shall not be discharged to the roof but shall be treated and then discharged to an approved plumbing fixture. Reference: Section 314.1, IPC 2018. 5. A temperature and pressure relief valve shall not discharge onto the roof but shall discharge to a termination point that is observable by the building occupants. Reference: Section 504.6, IPC 2108. |
||
06/23/2023 | PDSD Application Completeness | REVIEW COMPLETED |