Permit Number: TC-COM-0623-01535
Parcel: 141019140

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0623-01535
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/07/2023 Water - PDSD APPROVED
09/07/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
08/21/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 8/21/2023 9:02:39 AM

NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall
not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.




Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 8/18/2023 12:48:09 PM
1. Sheet A1.1: The egress balcony requires wall separation between the balcony and the structure. The exception of Section 1021.2 does not apply due to the dead end. Provide a properly rated wall between the egress balcony and the structure in accordance with Section 1021.2. See Section 1020.1, Section 708.3 w/ exceptions. Notate any exceptions on the plans. NOT COMPLIED.
◦ NOTE: The length of the dead end condition is not in question. A dead end condition less than 50' in length is permitted. The exception of Section 1021.2 states the separation is not required where the exterior egress balcony is served by not less than two stairways and a dead-end travel condition does not require travel past an unprotected opening to reach a stairway. The dead end travel that exists, travels past two unprotected openings (1 door and 1 window) and thus would require separation as required for corridors for Group R occupancies (1/2 hour for NFPA 13/13R systems) along with protected openings (doors and windows). Provide evidence of compliance that the walls and openings meeting the protection requirements of Section 716 and 1021.2.



Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 6/26/2023 11:21:05 PM
Approved/Subject to field approval for shell and core phase



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 8/17/2023 4:59:52 PM



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 8/18/2023 10:48:45 PM
Second Plumbing Review: ok subject to field inspections

1). Resolved-second floor water heater on plan page P4.1 needs to be in a pan and have its drains piped to a waste receptor or exterior. - IPC 504.6, 504.7. 504.7.2 ** added floor sink at water heater will need trap guard or trap primer, ok subject to
field inspections**
2). OK
3). OK
4). OK
5).OK
08/08/2023 Site Engineering REQUIRES RESUBMIT See zoning comment
08/08/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0623-01535
10455 E. Drexel Rd. - PAD-12
New Medical Office Building Shell (2nd Review)

TRANSMITTAL: August 8, 2023

Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in PAD-12 (UDC 4.7.24), Medical Office is an allowed use in the PAD.

1. Zoning has reviewed the building plans for compliance with the associated unapproved Development Package TD-DEV-0523-00235. Zoning cannot approve the building plans until the DP is approved.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/03/2023 PDSD Application Completeness REVIEW COMPLETED