Permit Number: TC-COM-0623-01496
Parcel: 113080240

Address:
2886 N 1ST AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0623-01496
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/29/2023 Site Engineering NOT REQUIRED
07/14/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
06/23/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0623-01496

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Structural(S) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 6/23/2023 8:07:08 AM
S2.0 – Show TJI span dimension in plan is it 29’-11” as shown in A1.0?
S2.0 and calculation – Keynote 1 shows “14 TJI 560 series rafters at 24” throughout…” yet calculation sheet 5 shows discrepancy of “TJI-560 (11 7/8”) @ 2’-0” O.C…”. Also roof span table in sheet 6 does not show span width over 29’-11”.
Calculation – Sheet 3: What is the risk category number determining the wind load per City of Tucson Amendments to the 2018 International Building Code?
Calculation - City of Tucson Amendments to the 2018 International Building Code adds new Section 1609.5.1.1 Uplift resistance to minimize microburst effects. Show the determination: 1. Design-based wind uplift criteria or 2. Prescriptivebased wind uplift criteria.

Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 6/23/2023 8:06:39 AM
A4.0 – Does not show new mechanical roof top unit such as evaporative cooler. Where is the roof access?

Mechanical(M) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 6/23/2023 8:06:54 AM
Mechanical
Roof equipment access not shown accordance with 2018 IMC section 306.3.
Plumbing
Missing plumbing plans: A1.0 keynote 12 and 13 states “refer to plumbing plan for additional information” but no plumbing plans were submitted



Electrical(E) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Approved
Reason:
Date Completed : 6/23/2023 8:06:23 AM
07/14/2023 Historic REQUIRES RESUBMIT Structure was built in 1947, therefore, minor historic demo documentation required. Application and checklist found here: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/planning-amp-zoning/historic_demolition_application_form.pdf
06/21/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-DMO-0623-01496
2886 N. 1st. Ave.
Partial Demo for Fire Damage Repair

TRANSMITTAL: June 21, 2023
COMMENTS: the following comments are relative to an application for Architectural Documentation prior to demolition of historic buildings (UDC 3.12.1).
& .10.

The Pima County Assessor’s effective construction date for your building or structure is 1947. The actual construction date may be earlier.
Buildings, portions of buildings or structures that are 50 years of age or older must be architecturally documented prior to demolition. Documentation will be reviewed and approved by the Historic Preservation Office before a permit is issued.
Demolition (Historic and Older Structures) Application and General Information may be downloaded (PDF) at https://www.tucsonaz.gov/pdsd/all-application-forms-submittal-requirements
Return completed documentation to PDSDHistoric@tucsonaz.gov. Applicant will be contacted within 5 working days if additional materials are required for review.
06/27/2023 Fire New Construction REVIEW COMPLETED
06/14/2023 PDSD Application Completeness REVIEW COMPLETED