Permit Number: TC-COM-0623-01487
Parcel: 117121290

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0623-01487
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/21/2023 Site Zoning APPROVED
06/29/2023 Site Engineering NOT REQUIRED
06/29/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
06/22/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0623-01487

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Structural(S) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 6/22/2023 8:05:37 AM
Structural calculation title shows 145 E. Congress, Tucson, AZ as the address. Are there two separate permits?
Sheet S2.0 – Sheet A1 partial demolition plan shows two stairs to be removed but only one stairs addressed in structural plan.

Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 6/22/2023 8:04:17 AM
Sheet C1 – Is fire alarm modification under separate permit? (deferred)
Sheet X1 – All rooms should be identified. New basement rooms are not identified and adjacent tenant work unidentified while it’s part of exit access through kitchen area #102 door.
Sheet X1 – Provide total building area (SF) and number of stories.
Sheet X1 – Basement floor plan does not match with M1 and P1 plans which shows additional rooms.
Sheet X1 – Show the dead-end corridor distance in basement floor code analysis plan. Does it meet 2018 IBC 1020.4 Dead ends requirement?
Sheet X1 – Show complete basement exit stairs. Only two risers are shown after the landing and coordinate with partial basement lighting plan clarifying the path of egress.
Sheet A1 – Provide demolition and new 2nd floor plan. Partial demolition plan shows stairways to be removed but does not show plan above. Sheet S2.0 only shows one stair to be removed so clarify the demolition scope. Clearly show up and down stairway directions.
Sheet A1.1 – Show room identifications in partial basement floor plan. A1.1 basement floor plan does not match with S2.0, M1 and P1 plans which shows additional rooms.

Mechanical(M) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 6/22/2023 8:04:50 AM
Sheet M1 – Mechanical basement floor plan does not coordinate with X1, A1, A1.1, and S2.0.

Electrical(E) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 6/22/2023 8:04:33 AM
Sheet E3 – Partial basement lighting plan have new rooms without lighting.
Sheet E3 – Basement plan do not coordinate with M1, P1 and P3 room layouts.

Plumbing(P) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 6/22/2023 8:05:04 AM
Sheet P1 and P3 – Plumbing basement floor plan do not coordinate with X1, A1, A1.1, and S2.0.
06/21/2023 Fire New Construction REVIEW COMPLETED
06/14/2023 PDSD Application Completeness REVIEW COMPLETED