Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
06/20/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 The electrical load calculations show 420 amps of new load. Please indicate all the equipment that the new loads are derived from. Panel 2 only shows 5.2 KVA of new load.

Ref; 2018 IBC sections 107.2.1, 2017 NEC.