Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0623-01481
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/20/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
06/20/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 The electrical load calculations show 420 amps of new load. Please indicate all the equipment that the new loads are derived from. Panel 2 only shows 5.2 KVA of new load. Ref; 2018 IBC sections 107.2.1, 2017 NEC. |
||
06/13/2023 | PDSD Application Completeness | REVIEW COMPLETED |