Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0623-01461
Parcel: 125080740

Address:
115 N TUCSON BL

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0623-01461
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2023 Commercial Structural APPROVED
06/12/2023 Site Zoning APPROVED
07/17/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
07/13/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical comments and provide a written response.

Per plan sheet PV1.0. The scope of work involves removing all the PV modules from both ‘A’ and ‘B’ roofs and relocating the 15 PV Modules from roof ‘B’ to roof ‘A’ and installing a new PV racking system. The note in the ‘SCOPE OF WORK Description’ states, “NO CHANGE TO DC OR AC ELECTRICAL CONFIGURATION”, “SEE T16CM00133 FOR ORIGINAL CONFIGURATION”. Due to the fact, that the reinstallation will require a degree of Electrical Engineering because of having to modify the string wiring to accommodate the merging of Roof ’B’ modules and Roof ‘A’ modules onto one roof ‘A’. And the installation of a new PV racking system, It is the determination of the City of Tucson Electrical plan Reviewer to require updated Electrical Plans and an updated PV system that meets the current NEC requirements, Including Rapid Shutdown requirements. Re submitted plans must have design, calculations and be sealed by an Arizona Registrant.

Be advised, if desired, the applicant may appeal to the Building Official for a variance to the plan Reviewers Comments. This is always an available option.

Ref; 2018 IBC section 107.1, 107.2.1, 2017 NEC.
06/09/2023 Fire New Construction REVIEW COMPLETED
06/08/2023 PDSD Application Completeness REVIEW COMPLETED