Permit Number: TC-COM-0623-01457
Parcel: 11612751B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0623-01457
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2023 Site Zoning APPROVED
06/16/2023 Site Engineering NOT REQUIRED
07/03/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/03/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0623-01457

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Structural(S) Reviewer
Janet Matz
jmatz@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 7/2/2023 12:52:17 AM
no structural work was included in this submittal


Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 7/2/2023 12:51:26 AM
1. Update the list of applicable codes to include the 2018 International Fuel Gas Code.
2. Add sheet A503 to the index on sheet G001 or remove it from the set.
3. Remove the “delivery drop zone” designation in front of the electrical panels on the life safety plan sheet G002. This area is part of the clear working space for the electrical panels as required in the 2017 NEC section 110.26 and can not be used for storage, even temporarily.


Mechanical(M) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 7/2/2023 12:51:47 AM


Electrical(E) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 7/2/2023 12:51:37 AM


Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 7/1/2023 1:55:37 AM
First Plumbing Review:
1). Plumbing Fixture calculations pending Building plan review of occupancy load and type. -IPC 403.1
2). Plan Page A103 states water heater is gas, plan page P-601 states water heater is electric? Plan pages need to correlate -IPC 106.3.1
3). Plan page P-103 roof condensate can't discharge to roof surface, will need to be routed to a receptor -IPC 314.2.1
06/15/2023 Fire New Construction REVIEW COMPLETED
06/14/2023 PDSD Application Completeness Express REVIEW COMPLETED