Permit Number: TC-COM-0623-01456
Parcel: 132191250

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0623-01456
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/21/2023 Site Engineering APPROVED
06/26/2023 Site Zoning APPROVED
06/22/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0623-01456

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Structural(S) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 6/22/2023 2:08:12 AM

Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 6/22/2023 2:07:22 AM

Mechanical(M) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 6/22/2023 2:07:43 AM

Electrical(E) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 6/22/2023 2:07:32 AM

Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 6/19/2023 10:20:48 PM
First plumbing review:
1). Mop sink on plan page P102 & P701 needs to discharge to the grease system . -Tucson Plumbing Code Amendments.
2). Schier website states the GB-75 is a Hydromechanical grease interceptor, per Tucson Plumbing Code Amendments no more than 4 items can discharge to a Hydro mechanical grease interceptor. Update all affected plumbing pages.
3). add piping material specs to plan page P001 -IPC 106.3.1, 605.4, 702
06/09/2023 Fire New Construction REVIEW COMPLETED
06/07/2023 PDSD Application Completeness REVIEW COMPLETED