Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0623-01432
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/13/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
06/13/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Provide for a Common Grounding Electrode System for the electrical services as required per NEC art 250.58. 2 The identification on the existing service disconnects do not correlate with the panels. For example; The disconnect identified as ‘Suite 111’ is connected to ‘Suite 109’. Please revise to correlate with each other. 3 Show the locations of all the panels and switchgears on the electrical site plan or power layout. 4 Identify the existing electrical service. Is it ‘SES 1’ ? 5 Provide total load calculations for ‘SES1’ ‘and SES2’ on plan sheet E4.1. 6 Include and identify all conduit, conductor quantities, sizes and types, for all the feeders. Ref; 2018 IBC section 107.2.1, 2017 NEC, |
||
06/02/2023 | PDSD Application Completeness | REVIEW COMPLETED |