Permit Number: TC-COM-0526-00771
Parcel: 10714091A

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0526-00771
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/28/2026 Commercial Mechanical Express APPROVED
05/28/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/27/2026 Addressing Validation REQUIRES RESUBMIT If you have questions regarding this review, please contact CDRC@tucsonaz.gov.

Please include the full property address on all construction plan documents and resubmit after other reviews are complete. You cannot resubmit during an active review.

Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf
05/28/2026 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0526-00771 (2532 N ESTRELLA AV TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide updated electrical load calculations, for the Main Panel showing it can support the additional electrical load, Per NEC 220.40.
2. Show a GFCI and weather protected receptacle outlet on the same level within 25’ of exterior HVAC equipment, NEC 210.62. New HVAC unit added to roof.
05/27/2026 PDSD Application Completeness Express REVIEW COMPLETED