Permit Number: TC-COM-0526-00770
Parcel: 11307118C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0526-00770
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2026 Commercial Electrical APPROVED
06/12/2026 Site Engineering APPROVED
06/10/2026 Site Zoning APPROVED Associated DP (TD-DEV-0425-00116) has been approved.
06/09/2026 Water - PDSD APPROVED
06/12/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/04/2026 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Please revise Sheet A000 as follows:
A. Remove the note under the "Tucson, AZ Notes" section, as it is not applicable to this project. The proposed design provides separate restroom facilities, the calculated occupant load exceeds 25 occupants, and the currently adopted code is the 2024 IBC. (IBC 107.2.1)
B. Update the referenced accessibility standard from ICC A117.1-2009 to ICC A117.1-2017. (IBC 107.2.1)
C. Revise the Occupant Load calculations, Occupant Load Factors, and Total Occupant Load to comply with IBC Table 1004.5. The exercise area shall be calculated using an occupant load factor of 50 gross square feet per person. Based on this factor, the design occupant load appears to be approximately 38 occupants.
The proposed restroom layout provides separate facilities, which satisfies the plumbing fixture requirements. Although the use is classified as Assembly Group A-3 in nature, IBC Section 301.1.1 states that a building or tenant space used for assembly purposes with an occupant load of fewer than 50 persons shall be classified as a Group B occupancy.

Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
06/09/2026 Commercial Mechanical REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0526-00770
ADDRESS/PARCEL: 3105 N CAMPBELL AV Unit:UNIT 115 TUCSON, AZ 85719
Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Show the size, routing, and termination of the condensate drains from the rooftop HVAC units. Reference: Section 307.2.1, IMC 2024 as amended by the City of Tucson.
06/09/2026 Commercial Plumbing REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0526-00770
ADDRESS/PARCEL: 3105 N CAMPBELL AV Unit:UNIT 115 TUCSON, AZ 85719
Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. The water meter serving this tenant space appears to be 1”, rather than the 2” meter shown on Sheet P1.0. Shell permit TC-COM-0725-01290 (Sheet P0.2) indicates a 1” meter serving this space. Please clarify the correct meter size and revise the plans as necessary. Reference: Section 107.2.1, IBC 2024.
2. Please show there are metering faucets for the lavatories dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10 seconds. Reference: Section 412.13, IPC 2024, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
3. A service sink is required in accordance with Table 2902.1. Please show on the plans. Reference: Section 2902.1, IBC 2024.
4. An additional submeter and backflow preventer have been added, which were not included in the water calculations under the shell permit (TC-COM-0725-01290). Demonstrate that the proposed water distribution system is adequately sized, accounting for pressure losses through the added equipment. The available water pressure in this area appears to range from approximately 46.04 psi to 53.04 psi as well. Reference: section 604.1, IPC 2024.
06/06/2026 Fire New Construction REQUIRES RESUBMIT Resolve all building comments.
john.vincent@tucsonaz.gov
5203495581
05/28/2026 PDSD Application Completeness Express REVIEW COMPLETED