Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.4
Permit Number - TC-COM-0526-00765
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/21/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/21/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0526-00765 ADDRESS/PARCEL: 3100 N STONE AV Unit:UNIT 122 TUCSON, AZ 85705 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov. COMMENTS: 1. The corridor is still being utilized as a return air path for the adjoining rooms. Corridors shall not be used as return air ducts unless one of the exceptions in Section 601.2 applies. Please revise the HVAC system to provide a return air path that does not utilize the corridor, such as providing return air from the individual rooms directly back to the HVAC unit. Reference: Section 601.2, IMC 2024. |
||