Permit Number: TC-COM-0526-00765
Parcel: 10711092A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0526-00765
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2026 Commercial Building Standard APPROVED
08/04/2026 Commercial Electrical Standard APPROVED
08/03/2026 Commercial Plumbing Standard APPROVED
08/05/2026 Site Zoning Standard APPROVED
08/05/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/03/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0526-00765
ADDRESS/PARCEL: 3100 N STONE AV Unit:UNIT 122 TUCSON, AZ 85705

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. The corridor is being utilized as a return air path for the adjoining rooms. Per Section 601.2, corridors shall not be used as return air ducts. An exception permits corridors to convey return air within tenant spaces of 1,000 square feet or less. Please revise. Reference: Section 601.2, IMC 2024.
08/05/2026 Fire New Construction Standard REVIEW COMPLETED
07/15/2026 PDSD Application Completeness Express REVIEW COMPLETED