Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0526-00765
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/04/2026 | Commercial Building Standard | APPROVED | |||
| 08/04/2026 | Commercial Electrical Standard | APPROVED | |||
| 08/03/2026 | Commercial Plumbing Standard | APPROVED | |||
| 08/05/2026 | Site Zoning Standard | APPROVED | |||
| 08/05/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/03/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0526-00765 ADDRESS/PARCEL: 3100 N STONE AV Unit:UNIT 122 TUCSON, AZ 85705 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov COMMENTS: 1. The corridor is being utilized as a return air path for the adjoining rooms. Per Section 601.2, corridors shall not be used as return air ducts. An exception permits corridors to convey return air within tenant spaces of 1,000 square feet or less. Please revise. Reference: Section 601.2, IMC 2024. |
||
| 08/05/2026 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 07/15/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |