Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2026 Commercial Electrical Standard APPROVED
06/11/2026 Site Zoning Standard APPROVED
06/08/2026 Commercial Mechanical Standard NOT REQUIRED
06/08/2026 Commercial Plumbing Standard NOT REQUIRED
05/29/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
06/02/2026 Site Engineering Standard NOT REQUIRED
06/08/2026 Water - PDSD Standard NOT REQUIRED
N/A Bldg Permits - Post Review Express PENDING ASSIGNMENT
N/A Fire New Construction Standard PENDING ASSIGNMENT
06/08/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov

1 Please indicate the following 2024 IBC 1010.2.11 Sensor release of electronically locked egress door requirements on the plans.


A. Upon a signal from a sensor or loss of power to the sensor, the electrical locking system shall unlock the electric lock.

B. Loss of power to the electric lock or the electrical locking system shall automatically unlock the electric locks.

C. The doors shall be arranged to unlock the electric lock from a manual unlocking device located 40 inches to 48 inches vertically above the floor and within 5 feet of the secured doors. Ready access shall be provided to the manual unlocking device and the device shall be clearly identified by a sign that reads “PUSH TO EXIT.” When operated, the manual unlocking device shall result in direct interruption of power to the electric lock—independent of other electronics—and the electric lock shall remain unlocked for not less than 30 seconds.

D. Emergency lighting shall be provided on the egress side of the door.

Please contact me if you have any questions about the above comments.